Remote Mount 5-Valves Manifolds, Model-HM8532

Using the 5-valve manifold_x000d_

_x000d_
In normal operation the “isolate” valves are open while the “equalize” and “vent” valves are closed. This provides a differential pressure reading to the pressure gauge or transmitter._x000d_

_x000d_
To zero the instrument, first close both “vent” valves and the downstream “isolate” valve. Then open the “equalize” valve and adjust the zero setting on the instrument._x000d_

_x000d_
To remove the instrument, first close both “isolate” valves, then open the “equalize” valves to relieve pressure between the manifold and the instrumet._x000d_

_x000d_
Note: The body & trim parts on all 316/316L Valves & Manifolds comply to NACE MR-01-75 & NORSOK M-650 as standard.

Tip

Hard, Soft

Weight_kg

2.7

Weight_Ib

5.95

Alloy

316/316L, 6%Mo, 625 INCONEL®, 825 INCONEL®, Carbon Steel, Duplex, HASTELLOY® C276, MONEL®, Super Duplex, Titanium, Titanium Blue Anodized

Calibration Option

An option provided by 5-valve manifolds which is not available on 3-valve types is connecting the "vent" port to known pressure sources to check the calibration of the instrument.

Inlet Connection

Female, Integral GYROLOK, Integral Metric, Socket Weld

Inlet Size

1/2" NPT, 1/2", 10 mm

Packing

GRAFOIL, PTFE